Anqiang Power is a China manufacturer of 66KV tank type SF6 circuit breakers. This tank-type SF6 circuit breaker is an outdoor high-voltage switchgear that combines the circuit breaker and current transformer. Users can add components such as disconnect switches, grounding switches, voltage transformers, and surge arresters as needed.
The 66KV Tank Type SF6 Circuit Breaker (Model: LW36-66) is a high-voltage outdoor circuit breaker designed for 66KV power transmission and distribution systems with a rated frequency of 50Hz AC. Utilizing SF6 gas as both the insulating and arc-extinguishing medium, it provides reliable switching, fault interruption, and protection for substations, utility power grids, industrial facilities, and renewable energy projects. The circuit breaker can also be used as a bus tie breaker and for capacitor bank switching applications.
Designed with a compact live-tank structure, the LW36-66 minimizes installation space while delivering outstanding electrical performance and long-term operational reliability. Its advanced spring operating mechanism, low SF6 leakage rate, and maintenance-friendly design make it an ideal solution for modern high-voltage transmission networks requiring safe, efficient, and stable operation.
Actual Product Photo
Product Dimensions Diagram
Main Structure
Silver-plated aluminum single-phase terminal block for excellent electrical conductivity.
High-strength porcelain outgoing bushing with superior insulation performance.
Built-in current transformer (CT) for protection and measurement.
Floor-mounted SF6 arc extinguishing chamber with high interrupting capability.
Mechanism cabinet integrating the spring operating mechanism and secondary control components.
Heavy-duty galvanized channel steel support for stable installation.
Multiple grounding terminals for improved operational safety.
Product Features
Rated current up to 3150A, suitable for heavy-load transmission applications.
Advanced SF6 gas insulation technology ensures excellent dielectric strength and reliable arc extinction.
Long electrical endurance with 31.5kA fault interruption capability and up to 10,000 mechanical operations.
Annual SF6 gas leakage rate below 0.5%, reducing maintenance requirements and ensuring long-term sealing reliability.
The 66KV Tank Type SF6 Circuit Breaker is designed for severe outdoor environments, supporting Pollution Level IV and ambient temperatures from -40°C to +40°C.
Compact tank-type construction reduces installation space while improving mechanical stability.
Suitable for remote monitoring, substation automation, and modern smart grid applications.
Technical Specifications
Rated Voltage
66KV
Rated Frequency
50Hz
Rated Current
3150A
Power Frequency Withstand Voltage (5 min)
84KV
Rated Short-Circuit Breaking Current
31.5kA
Rated Short-Circuit Making Current (Peak)
80kA
Rated Peak Withstand Current
80kA
Rated Short-Time Withstand Duration
4s
Rated Out-of-Step Breaking Current
8kA
Rated Line Charging Current
10A
Rated SF6 Gas Pressure (20°C)
0.5MPa
Annual SF6 Leakage Rate
<0.5%
Mechanical Life
10,000 times
SF6 Gas Filling Quantity
10kg
Circuit Breaker Weight
1800kg
Operating Mechanism Specifications
Auxiliary Circuit Voltage
DC220V / DC110V
Opening & Closing Coil
DC110V / 4A, DC220V / 2A
Motor Charging Time
≤15s
Heater & Lighting Voltage
AC220V
Auxiliary Switch Voltage
DC220V / AC220V
Auxiliary Switch Current
10A
Energy Storage Motor Power
600W
Applications
The 66KV Tank Type SF6 Circuit Breaker is widely used in high-voltage power transmission and distribution systems where reliable switching and protection are essential.
66KV substations
Utility transmission and distribution networks
Power generation plants
Renewable energy grid integration
Industrial power distribution systems
Capacitor bank switching
Bus tie and feeder protection
Smart grid and substation automation projects
Working Principle
The 66KV Tank Type SF6 Circuit Breaker uses sulfur hexafluoride (SF6) gas as both the insulating and arc-quenching medium. When the contacts separate during a switching operation, an electric arc is generated. High-pressure SF6 gas rapidly cools and deionizes the arc, allowing the fault current to be interrupted safely and efficiently. The motor-charged spring operating mechanism provides fast opening and closing operations, ensuring reliable protection for high-voltage electrical systems.
Frequently Asked Questions
What is a 66KV Tank Type SF6 Circuit Breaker used for?
It is used for switching, protection, and fault interruption in 66KV transmission and distribution systems, helping maintain the safe and reliable operation of substations and power grids.
What are the advantages of an SF6 tank type circuit breaker?
SF6 tank type circuit breakers offer excellent insulation performance, high interrupting capacity, compact structure, low maintenance requirements, and long mechanical service life.
Can this circuit breaker be used for capacitor bank switching?
Yes. The LW36-66 is suitable for capacitor bank switching, bus tie applications, and high-voltage transmission line protection.
Is the circuit breaker suitable for harsh outdoor environments?
Yes. It is designed to operate reliably under Pollution Level IV conditions and ambient temperatures ranging from -40°C to +40°C, making it suitable for demanding outdoor installations.
Hot Tags: 66KV Tank Type SF6 Circuit Breaker Manufacturer, High Voltage Circuit Breaker Supplier, Tank Type Circuit Breaker Manufacturer
For inquiries about Circuit Breaker, Load Switch, Disconnect Switch or price list, please leave your email to us and we will be in touch within 24 hours.
We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies.Privacy Policy